/ Simulating Input Signals with Force Table
/
Set Force Value
Click on the cell in the Force value column and type in the value you want the signal to have. When forcing an analog input please note before any scaling to engineering values the range fo the signal is always 0 - 27648d (0 - 6C00h).
Example: If the measurement scale in engineering values would be 100 - 460 °C you'll get
- 100 °C by forcing 0 to the analog input;
- 460 °C by forcing 27648 to the analog input;
- and other temperatures interpolating according to a linear function
Updated 7.10.2019