I/O Table Error
Problem: A red I/O-table error bar is blinking at the bottom of CX Programmer screen.
Reason: CX Programmer and PLC have different I/O hardware configuration
Solution:
- Change to Online Mode: PLC -> Work Online (CTRL-W)
- Change PLC to Program Mode: PLC -> Operating Mode -> Program (CTRL-1)
- Open I/O Hardware Configuration window: PLC -> Edit -> I/O Table
- In the opened window, remove current I/O definition: Options -> Delete (if Delete cannot be selected, go through the previous stages again)
- Load the I/O Configuration from the PLC: Options -> Transfer from the PLC
- If the fault is still not cleared, reset the PLC by switching the power off for at least ten seconds