timohei.net / My Courses / TL110103 PLC Control 3 cu / Exercise: Steam Soot Blower /
PLC Connections: Outputs
Local Control Panel

Define the addresses as XXX.0Y where XXX is the PLC specific word address (010 for CPM, 100 for CQM, and 000 for CJ1M) and Y is taken from the numbered list below!

  1. IN
    • an indicator lamp at the local control panel
    • constantly lit if IN limit switch is activated
    • blinks with 1 Hz frequency while the soot blower motor is running to IN direction
  2. "OUT"
    • an indicator lamp at the local control panel
    • constantly lit if OUT limit switch is activated
    • blinks with 1 Hz frequency while the soot blower motor is running to OUT direction
  3. DISCREPANCY
    • an indicator lamp at the local control panel
    • blinks with 1 Hz frequency if there is a running time or limit switch discrepancy that is not yet acknowledged
    • running time discrepancy = the soot blower does not reach its limit switch within 20 s after motor control has been activated
    • limit switch discrepancy = both limit switches are activated at the same time
    • any discrepancy initiates an immediate retraction of the soot blower
  4. STEAM
    • an indicator lamp at the local control panel
    • constantly lit if there is enough steam flow (STEAM sensor witch is activated)
    • starts to blink in case of steam discrepancy (meaning the steam flow was interrupted while the IN limit switch was not activated)
      1. steam discrepancy appears -> blink fast with 1 Hz and 5 Hz inputs in series
      2. discrepancy is acknowledged (input 4) -> blink slowly (1 Hz only)
      3. discrepancy is acknowledged and the failure clears out -> back to normal, the lamp indicates the status of the steam flow sensor. Note that the failure can be cleared out in two ways: the steam starts to flow again or the soot blower enters IN limit
      4. steam discrepancy is not acknowledged and the failure clears out -> the lamp continues fast blinking until steam acknowledge button is pushed
    • any discrepancy initiates an immediate retraction of the soot blower
  5. IN LIMIT
    • contol output to the Electric Control Center (ECC)
    • ECC feeds the soot blower motor according to this output causing it to turn to IN direction
    • the output has to be activated the whole running time
  6. OUT LIMIT
    • contol output to the Electric Control Center (ECC)
    • ECC feeds the soot blower motor according to this output causing it to turn to OUT direction
    • the output has to be activated the whole running time
  7. STEAM VALVE
    • contol output to the steam valve
    • the valve is opened and stays open whenever this output is activated and closes when this output is deactivated
    • is activated as soon as START button (input 1) is pushed
    • is deactivated as soon as the soot blower reaches IN limit

Updated 13.2.2008