timohei.net / My Courses / TL110103 PLC Control 3 cu / Excercise: Valve Control /
PLC I/O: Inputs

K = Closed
A = Opened
OHJAUS = CONTROL
LIIKKUU = MOVING
VALVONTA-AIKA = DISCREPANCY
- Control Switch "Closed/Opened"
- A turning switch in the Local Panel
- Activates driving of the valve to open or closed position
- Input switch in open position (0) -> the valve is closed
- Input switch in closed position (1) -> the valve is opened
- Limit Switch "Closed"
- A limit switch at the valve
- the switch is closed only when the valve is fully closed
- both limit switches are open when the valve is in an intermediate position
- Limit Switch "Opened"
- A limit switch at the valve
- the switch is closed only when the valve is fully opened
- both limit switches are open when the valve is in an intermediate position